Table 13-3. Example of savings with installation of automatic blowdown equipment (basis: one day).

Evaporation 2,400,000 lb/day
Boiler Pressure: 600 psig
Manual blowdown:  183,423 lb/day (7.1%)
Automatic blowdown:  145,069 lb/day (5.7%)
Blowdown Reduction:  38,354 lb/day
Feedwater temperature: 240 °F
Makeup water temperature: 60 °F
Heat of liquid at 600 psig 475 Btu/lb
Heat of liquid at 60°F -28 Btu/lb
Heat required: 447 Btu/lb
     (blowdown reduction) X 38,354 lb/day
Heat reduction: 17,144,238 Btu/day
Fuel (gas): 1,040 Btu/ft3

      (@ 80% boiler efficiency)

X .80

Available fuel heat: 832 Btu/ft3
       (heat reduction) 17,144,238 Btu/day

 

÷ 832 Btu/ft3
Fuel reduction: 20,606  ft3/day
Fuel savings @ $4.00/1000 ft3: $ 82.42
Labor reduction: 0.5 hr
Daily labor savings @ $30.00/hr $ 15.00
Water reduction: 4,598 gal/day
Daily water savings @ $ 0.80/1,000 gal: $ 3.68
Total daily savings: $101.10
X 365 days/yr
Annual savings $36,902